ANALISA PECAH PENYULANG METRO DI UNIT LAYANAN PELANGGAN TANJUNG PANDAN
DOI:
https://doi.org/10.33019/snppm.v3i0.1322Keywords:
End Voltage, new feeder, Length of Feeder and Load Flow simulation SoftwareAbstract
In an electric power system has a base voltage and end voltage, where at the end of the network has a decrease in voltage. The standard set for the minimum voltage allowed at the end is 19 kV in accordance with the SPLN. The case study taken is a feeder with the name metro which is one of the feeders who has a below-standard mark of value at the PLN Pandan Tanjung Service Unit.The calculation of the analysis discussed using load flow simulation software by simulating the metro feeder in accordance with the field, then make 3 schemes ideal conditions that can improve the tip stress on the metro feeder.From the simulation results, the best ideal conditions for follow-up repairs can be obtained based on the value of the feeder tip voltage by calculating the cost of the investment based on the length of the feeder being built.